Pump Characteristics - Carrier Aquaforce 30XA302 Installation, Operation And Maintenance Instructions

Air-cooled screw chillers
Hide thumbs Also See for Aquaforce 30XA302:
Table of Contents

Advertisement

30XA with configuration: Leaving water control
1

7.7 - Pump characteristics

7.7.1 - Available external static pressure (hydronic module option)
Data applicable for:
- Fresh water 20 °C
- In case of use of the glycol, the maximum water flow is reduced.
- When the glycol is used, it's limited to 40%.
Low-pressure pumps (options 116F/116G)
200
502
175
452
150
125
100
75
50
25
0
3
5
7
9
11
7.7.2 - Net positive suction head (NPSH) required, hydronic
module option
Size the hydronic circuit to ensure a net positive suction
head that is higher than or equal to the required NPSH +
50 kPa.
Low-pressure pumps (options 116F/116G)
80
70
60
50
40
30
20
10
252-302
0
3
5
7
9
11 13 15 17 19 21 23 25 27 29 31 33 35
2
402
352
302
252
13
15
17
19
21
23
Water flow rate, l/s
452 -502
402
352
Water flow rate, l/s
Legend
Master unit
1
Slave unit
2
Control boxes of the master and slave units
Water inlet
Water outlet
Water pumps for each unit (included as standard for units with hydronic
module)
Additional sensors for leaving water control, to be connected to channel 1 of
the slave boards of each master and slave unit
CCN communication bus
Connection of two additional sensors
High-pressure pumps (options 116B/116C)
400
375
350
325
300
275
250
225
200
175
150
125
100
75
50
3
5
25
27
29
Data applicable for:
- Fresh water 20 °C
- In case of use of the glycol, the maximum water flow is
reduced.
- When the glycol is used, it's limited to 40%.
High-pressure pumps (options 116B/116C)
120
100
80
60
40
20
0
3
5
252
402
352
302
7
9
11
13
15
17
19
Water flow rate, l/s
252
302 - 352
7
9
11 13 15 17 19 21 23 25 27 29 31 33 35
Water flow rate, l/s
452
502
21
23
25
27
29
31
452 -502
402
35