Installing the VVT Zone II

To wire the T55 sensor to the controller

Part #33ZCT55SPT
This wall-mounted sensor monitors space temperature and can be used instead of a ZS or wireless sensors.
1
Strip the outer jacket from the cable for at least 3 inches (7.62 cm). Strip .25 inch (.6 cm) of insulation from
each wire. Cut the shield and drain wire from the cable.
2
Wire the sensor to the controller, attaching the red wire to the T55 (Opt) terminal and the black wire to the
Gnd terminal. See diagram below.
3
Verify that the T55 (Opt) jumper is in the Thermistor position.

To wire the Supply Air Temperature sensor to the controller

Part #33ZCSENSAT
Each VVT Zone II requires that a temperature sensor be installed in the supply air stream. Mount the SAT sensor
at least 2 feet downstream from a hot water or steam coil, or at least 4 feet downstream from an electric heating
coil.
Wire the sensor to the controller. See diagram below.