Wiring a Supply Air Temperature sensor

Part #33ZCSENSAT
The VVT Zone Controller requires a temperature sensor installed in the supply air stream. The Supply Air
Temperature (SAT) sensor is used when the zone controller is equipped with ducted heating.

Wiring specifications

Cable from sensor to controller:
Maximum length:

To wire the SAT sensor to the controller

Wire the sensor to the controller. See diagram below.
1
Verify that the Enable SAT jumper is on.
2
Verify that the Enable SAT and REMOTE jumper is in the left position.
3
VVT Zone Controller
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
22 AWG, unshielded
22 AWG, shielded
15