● Default of the port
– Open
– Closed
– Open
– Open after configuration
– Open (login, when configured)
– Closed after configuration
● Authentication
Specifies whether or not the protocol authenticates the communications partner during
access.
Protocol / function Port number (pro-
tocol)
DNP3
20000 (TCP)
IEC
102 (TCP)
S7 and online
2404 (TCP)
connections
Online security
8448 (TCP)
diagnostics
Communication
8448 (TCP)
via SINEMA RC
HTTP
80 (TCP)
HTTPS
443 (TCP)
SNMP
161 (UDP)
* For information on avoiding opening the port during diagnostics, see section Online
security diagnostics via port 8448 (Page 174).
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
The port is open at the start of the configuration.
The port is closed at the start of the configuration.
Port status
The port is always open and cannot be closed.
The port is open if it has been configured.
As default the port is open. After configuring the port, the communications partner
needs to log in.
The port is closed because the CP is always client for this service.
Default of the port
Closed
Closed
Open
Closed
Closed
Closed
Closed
Open
Port status
Open after configuration
Open
Open after configuration *
Open after configuration
Open after configuration
Open after configuration
Open after configuration
Open after configuration
Configuration
4.1 Security recommendations
Authentication
Yes, when secure
authentication is ena-
bled.
No
No
No
Yes
Yes
Yes
Yes (with SNMPv3)
57