Choosing an Installation Site

• Do not install the unit more than 6 cm above the floor.
• Before choosing the installation site, obtain user approval.
1.

Indoor unit

• The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air intake and exhaust have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the
remote controller range,
8) the unit is at least 1 metre away from any television or radio set (unit may cause interference with the picture or sound).
• Pipework shall be protected from physical damage, which could potentially happen during normal operation, service
or maintenance.
• Pipework shall only be installed in a room smaller than the minimum size as defined in the table below if the pipes
have no connecting joints and do not have bends with a centerline bend radius less than the minimum bend radius
mentioned in chapter 6-2. Selection of copper and heat insulation materials.
• Floor area where the indoor unit will be installed shall be higher than minimum required floor area mentioned in table
below.
Minimum floor area for indoor unit.
m
[kg]
c
0.70
0.76
0.86
0.96
1.06
1.16
1.26
1.36
1.46
1.56
1.66
1.76
1.84
1.94
2.04
2.14
2.24
2.34
9
8
7
6
5
4
3
2
1
0
1.84
2.04
4
2
A
[m
min
No requirements.
3.63
3.83
4.03
4.22
4.42
4.62
Installation requirements
2.24
2.44
2.64
2.84
Mass of refrigerant [kg]
Minimum floor area for indoor unit.
m
[kg]
]
c
2.44
2.54
2.64
2.74
2.84
2.94
3.04
3.14
3.24
3.34
3.44
3.54
3.64
3.74
3.84
3.94
4.04
4.14
3.04
3.24
3.44
3.64
6 cm
A
[m
min
4.82
5.01
5.21
5.41
5.61
5.80
6.00
6.20
6.40
6.59
6.79
6.99
7.19
7.38
7.58
7.78
7.98
8.17
3.84
4.04
2
]