Commissioning - Siemens SINAMICS G120 Getting Started

Converter with control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning

4.3 Commissioning
4.3
Commissioning
Commissioning is carried out with the IOP using one of the "basic commissioning wizards
(Page 36)". If the IOP does not contain the actual frequency converter software, a message
is displayed "Update is required". You can find the required information on the Internet at
"http://support.automation.siemens.com/WW/view/de/67273266
(http://support.automation.siemens.com/WW/view/en/67273266)".
In the basic commissioning, select the control mode for the motor, enter the motor data and
define the pre-assignment of the frequency converter interfaces. You can find the
corresponding wiring in section "Default settings of the terminal strip (Page 28)".
Overview of the commissioning
● When commissioning with wizards, the first step is to RESET to the factory settings. This
ensures that the frequency converter is in a defined basic setting.
After the basic commissioning, the wizard that you selected guides you through the
application-specific settings.
● Before the frequency converter accepts your commissioning data, you must check these
and confirm them. You do this using the last but one menu item OVERVIEW OF THE
SETTINGS. In this screen, scroll down to CONTINUE and acknowledge it with OK.
● The last step is the prompt SAVE or INTERRUPT WIZARD? Select SAVE!
Commissioning using the wizards has now been completed.
● You can subsequently change your converter settings (Section "The most important
parameters at a glance (Page 42)").
● Once you have completed commissioning, you should back up the settings of your
frequency converter e.g. on the IOP, so that they are not lost if the frequency converter
develops a defect.
38
Motor frequency (P0310)
Motor voltage (p0304)
Motor current (P0305)
Motor power (P0307)
Rated motor speed (P0311)
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 04/2014, A5E32885834B AB

Hide quick links:

Advertisement

Table of Contents
loading