Duct Connections; Refrigerant Piping; Brazing To Evaporator - Trane 2/4TEC3F18B1000A Installer's Manual

Convertible air handlers 1-1/2-5 ton
Table of Contents

Advertisement

Installer's Guide
w
Flange Attachment
d. If the unit is not suspended it must be isolated
carefully to prevent sound transmission. Vibra-
tion isolators (purchased locally) must be placed
under the unit.
e. It is always recommended that an auxiliary drain
pan be installed under a horizontal air handler
(See Condensate Drain Piping) to prevent pos-
sible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or
from the structure.
g. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and ter-
minate according to local codes.
h. If a return duct is connected to the Air Handler,
it must be the same dimensions as the return
opening shown in the outline drawings.
i. On units with sheetmetal returns: Return ple-
num should be flanged. Sheetmetal screws must
be 1/2" in length or shorter.
j. No sheetmetal screws may be used to attach re-
turn ductwork on the side of the unit.
k. Openings where field wiring enters the cabi-
net must be completely sealed. Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electri-
cal knockouts and cage nut openings. See Figure
11.
l. After ductwork connections are made, seal air-
tight and per local codes.
D. DUCT CONNECTIONS
The supply and return air ducts should be connected to
the unit with flame retardant duct connectors.
8
Convertible duct flanges are provided on the discharge
opening to provide a "flush fit" for 3/4" or 1-1/2" duct
board applications. See the Outline drawing for sizes of
the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.
NOTE: No sheetmetal screws may be used to attach re-
turn ductwork on the side.
NOTE: On units with sheetmetal returns: Return plenum
should be flanged. Sheetmetal screws must be 1/2" in
length or shorter. See Figure 12.
NOTE: If the convertible duct flanges are not used, they
must be removed and discarded for proper airflow.
NOTE: Any duct board return connection can be made
to the sides of the unit using tape or mastic.
E. REFRIGERANT PIPING
IMPORTANT:
Refrigerant piping must be routed to maintain service ac-
cess to blower compartment and provide easy removal of
filter access panel and filter.
1. Refrigerant connections are made outside the cabi-
net.
NOTE: TXV bulb MUST be protected (wrap a wet rag
around the suction line between the TXV bulb and the
braze joint) or removed, while brazing the tubing. Over-
heating of the sensing bulb will affect the functional
characteristics and performance of the air handler.
NOTE: The area around refrigerant lines must be
sealed and electrical inlets need to be sealed at both
the low and the high voltage.
2. Installation of refrigerant lines is covered in the in-
stallation instructions packaged with the outdoor
unit. Evacuation, leak testing and brazing proce-
dures are included in those instructions. Read those
instructions before starting installation of refriger-
ant lines.
NOTE: Torque specification for TXV equals 1/6 turn past
finger tight.
F. BRAZING TO EVAPORATOR
NOTE: A brazing shield is provided in the information
pack accompanying this unit. This shield fits over the
refrigerant fittings while brazing. Wet the shield before
brazing. See Figure 13.
IMPORTANT:
Do NOT unseal refrigerant tubing until ready to cut and fit
refrigerant lines.
1. Remove the sealing caps from indoor coil field
connections.
18-GE08D1-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents