4.3. Analog Input Object

Analog Input Object is used for the output frequency of VF-PS1, and the monitor of
analog input terminal. COS (Change Of State) alarm and warning functions are also
enabled.
Overriding of analog input is not supported ("A" response).
Table 4 Analog Input Objects Table
Object
number
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
*
Reserved (The response is "A").
**
Refer to section 5 about the trip code of VF-PS1.
***
These are enabled with ETB004Z (Expansion IO Card option).
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Object
name
OUTPUTSPEED
OUTPUTFREQ
DCBUSVOLT
OUTPUTVOLT
CURRENT
TORQUE
POWER
DRIVETEMP
KWH
RUNTIME
LASTFLT
PREVFLT1
PREVFLT2
MBOXVALUEREAD
A1ACT
*
-
AI2ACT
AI3ACT
AI4ACT
***
AI5ACT
***
*
-
*
-
PRCPIDFBCK
Contents
Output speed
Output frequency
DC bus voltage
Motor voltage
Motor current
Motor Torque
Motor Power
Drive Thermal State
Input Energy counter
Operating time
Error code
**
Previous fault 1
Previous fault 2
Refer to section 4.9.
Analog input value 1 (RR/S4)
-
Analog input value 2 (VIB)
Analog input value 3(RX)
Analog input value 4(AI1)
Analog input value 5(AI2)
-
-
PID feedback value
- 13 -
E6581540
Units
-1
min
Hz
V
V
A
%
%
%
kWh
h
-
**
-
**
-
-
-
-
-
%
%
%
-
-
%