System Specifications
Power Input Requirements
The following table lists the typical amount of power consumed by the switch and its power supply and the
maximum amount of power that you must provision from the power source as input to the power supply and
switch for peak conditions.
Table 1: Switch Power Input Requirements
Cisco Nexus 9396PX
Power Cord Specifications
If you are using a DC power supply, we recommend using a 8 AWG insulated cable (10 AWG minimum)
customer-supplied cable to wire each power supply to its power source and the earth ground. If you are using
an AC power supply, see the following table for the power cord specifications.
Table 2: AC Power Cord Specifications
Locale
Argentina
Australia
Brazil
European Union
India
Israel
Italy
North America
Power Cord Part Number
CAB-C13-C14-2M
CAB-C13-C14-AC
CAB-C13-CBN
CAB-250V-10A-AR
CAB-9K10A-AU
CAB-250V-10A-BR
CAB-9K10A-EU
CAB-IND-10A
CAB-250V-10A-IS
CAB-9K10A-IT
CAB-9K12A-NA
Cisco Nexus 9396PX NX-OS-Mode Switch Hardware Installation Guide
Typical Power
Consumption
232 W
Cord Set Description
Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m)
Power cord, C13 to C14 (recessed receptacle), 10 A, 9.8 feet
(3 m)
Cabinet jumper power cord, 250 VAC, 10 A, C14-C13
connectors, 2.3 feet (0.7 m)
250 V, 10 A, 8.2 feet (2.5 m)
250 VAC, 10 A, 3112 plug, 8.2 feet (2.5 m)
250 V, 10 A, 6.9 feet (2.1 m)
250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m)
10 A, 8.2 feet (2.5 m)
250 V, 10 A, 8.2 feet (2.5 m)
250 VAC, 10 A, CEI 23-16/VII plug, 8.2 feet (2.5 m)
125 VAC, 13 A, NEMA 5-15 plug, 8.2 feet (2.5 m)
Power Input Requirements
Maximum Power
Consumption
455 W
47