Step 4
Turn on the circuit breaker for the DC power source connected to the power supply and verify that the power supply
LED turns on and becomes green.
For information on what the power supply LEDs indicate, see

Wiring a 48 V DC Electrical Connector Block

You must connect the ground, negative, and positive DC power cables to a connector block in order to connect
the power cables to a 48 V DC power supply.
Note
The recommended wire gauge is 8 AWG. The minimum wire gauge is 10 AWG.
Statement 342—Before Connecting to System Power Supply
Warning
High leakage current earth connection essential before connecting to system power supply.
Statement 1024—Ground Conductor
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available.
Before You Begin
You must turn off the circuit breaker for the DC power cables that you are connecting to prevent electrocution.
Step 1
Verify that the circuit breaker for the DC power source you are connecting is turned off.
Step 2
Remove the DC power connector block from the power supply by doing the following:
a) Push the orange plastic button on the top of the connector block inward toward the power supply.
Wiring a 48 V DC Electrical Connector Block
Power Supply LEDs, on page
Cisco Nexus 9396PX NX-OS-Mode Switch Hardware Installation Guide