9.2.4 Parameter Assignment
X, y
x =
x = Data block number (DB)
: KS = P
Normal 1/0 area
P/Q
Extended 1/0 area
KS = Q
PAFE : In case of illegal parameterization the signal status is"1". The recognized error is
then shown by the assignment of the flag byte FY 255:
F 255.0
The module address is outside of the specified area or not within the
8–bit grid pattern (first part of parameter BGDB).
The parameter P/Q is not set with 'P-' or
F 255.1
(not for programmable controller S5-115U)
The specified user data block number is zero or one.
F 255.2
(one only for S5-155U andS5-115U)
(second part of parameter BGDB)
F 255.3
The specified user data block does not exist or is too short.
(second part of parameter BGDB)
F 255.4
QVZ, no module found under this address.
(first part of parameter BGDB)
(only for S5-155U and S5-135U)
F 255.5
When the "verify–read (PR)" or "calculate average value (MB)"
special function is enabled, the "number" parameter is located
(outside the permissible area from O to 15) in data word DR 182 or DR
184 of the user data block.
F 255.6
F 255.7
SPFE : Is set, if after an access the SP bit is not reset by the module within a specified
time interval.
9 – 4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Module address (BG)
128<
X <248
0 <
X <248
1< y <255
2 < y <255
for S5– 155U and S5– 135U
for P/Q : KS=P
for P/Q: KS=Q
'Q–'