Trim the transmitter
Devices are calibrated by the factory. Once installed, it is recommended to
perform a zero trim on the sensor to eliminate error due to mounting position
or static pressure effects.
This can be done by performing a zero trim via:
•
LOI – see
•
Class 2 master – see
6.1
Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Basic Setup > Calibration and set the lower calibration point to
0.0.
4. Place the transducer block to AUTO mode.