2

Housing rotation

To improve field access to wiring or to better view the optional LCD display:
Figure 2-1: Housing Rotation
A. Housing Rotation Set Screw (5/64-inch)
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate
the housing counterclockwise to the desired location (up to 360° from
thread limit).
4. Re-tighten the housing rotation set screw to no more than 7 in-lbs
when desired location is reached.
10 Rosemount 2051 Pressure Transmitter and Rosemount 2051CF Series Flowmeter Quick Start Guide