LME Series
Honeywell Modutrol IV with the LME75 (continued)
Setup Procedure with Valve Proving
1. The following procedure should be used when valve proving is being utilized.
2. Set the following parameters in the LME75 as described below:
Parameter 241 = 1
Parameter 259 = Greater than or equal to the running time of the Honeywell
Parameter 260 = Greater than or equal to the running time of the Honeywell
Parameter 515.01 = 1
Parameter 560 = 0
3. Wire the LME75.000A1 burner control, Honeywell Modutrol IV motor, and four relays as
shown in Figure A-2. See Section 4 for more details on how to wire in other devices to
the LME75.