Synchronizing the LME7 and PME Parameters

The ACS410 software can be used to synchronize the parameter set used by the LME7 and the
backup copy stored on the PME chip.
1. Ensure that the ACS410 software is open, and the PC is connected to the LME7 at the
service or OEM level. See previous sections if necessary.
2. Click on the "PME Backup / Restore" tab.
3. To overwrite the parameter backup that is stored on the PME chip with the current LME7
parameters, click on "Backup". A window will appear asking if you are sure you would like to
procced with the backup. Click "Yes". The backup takes approximately one minute. After the
backup is complete, the LME7 will display "bAC End" which means that the backup is complete.
A reset of the LME7 burner control is required to get rid of the "bAC End" message.
4. To overwrite the current LME7 parameters with the parameter backup that is stored on the
PME chip, click on "Restore". A window will appear asking if you are sure you would like to
procced with the restore. Click "Yes". The restore takes approximately one minute. After the
restore is complete, the LME7 will display "rSt End" which means that the restore is complete.
A reset of the LME7 burner control is required to get rid of the "rSt End" message.