Description Of The High And Low Pressure Switch Function - Master AC 24 Installation Manual

Table of Contents

Advertisement

Introduction
System protection
Reset
LP (low pressure)
HP (high pressure)
18

Description of the high and low pressure switch function

This topic describes the HP/LP function.
The cooling system is protected by pressure switches. If the pressure falls outside of the
normal operating range, the air conditioner compressor is automatically switched off. This is to
prevent component damage. If the pressure is too high or too low, the unit is switched off. The
malfunction must normally be identified by a trained technician and corrected.
The HP/LP pressure switch automatically resets after a few minutes.
If the lamp continues to illuminate, please refer to the "Fault finding guide".
The cooling system is protected by a low-pressure switch (LP switch). The switch is set at 1 bar
and will automatically reset at 2.5 bar. The safety function cuts off the com-pressor.
The LP function will be activated if:
The cooling system loses refrigerant
The internal temperature is so low that the low pressure gets below set point (1 bar).
Do not operate the product with frequent operating LP function.
The evaporator is blocked or does get not sufficient air flow
The cooling system is protected by a high-pressure switch (HP switch). The switch is set at 25 bar
and will automatically reset at 18 bar. The safety function cuts off the compressor.
The HP function will be activated if:
The outdoor temperature is too high
The condenser is blocked or does not have sufficient airflow