LP, Indoor unit.
Indoor Standby LED, flash 23 times
.
(Indoor & Outdoor units don't match)
# Check if the Indoor & Outdoor units are correctly matched.
Note: If the indoor & outdoor units are from two different model types, the LP fault code will be
displayed.
C5, Indoor unit.
Indoor Standby LED, flashing 15 times.
(Jumper Cap Malfunction)
# Check the Jumper Cap for correct termination to the indoor PCB.
Note: If the Jumper Cap is correctly terminated, yet the C5 fault still exists, replace the indoor PCB
assembly.
Note: If the replacement indoor or outdoor PCB is from a different model, LP fault code will be
displayed.
Jumper Cap location on indoor PCB.
Page 27 KSSSI113