Fitting The Coaxial Flue (Ø 60/100 Horizontal) - Ariston CLAS HE R Installation And Servicing Instructions

Condensing wall-hung gas boiler
Table of Contents

Advertisement

Warning
The exhaust gas ducts must not be in contact with or close to
inflammable material and must not pass through building structures
or walls made of inflammable material.
When replacing an old appliance, the flue system must be changed.
Installation with extension
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall, fit the rubber flue
seal into the internal flue turret (see diagram opposite),
Insert the elbow into the socket and rotate to the required position.
note: It is possible to rotate the elbow 360° on its vertical axis.
Using the flue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal flue kit (3318073) supplied is suitable for an
exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face
of the flue elbow (X - Fig 2), this figure must now be subtracted from
753mm, you now have the total amount to be cut from the plain
end of the flue.
Important
Ensure that the flue is not blocked.
Ensure that the flue is supported and assembled in accordance with
these instructions.
Installation without extension
slope
* pente
Note: A Plume management kit is available for 60/100 horizontal
termination. Instructions for installation are supplied with the
Plume management kit.
Draw a circle around the outer flue and cut the flue to the required
length taking care not to cut the inner flue, next cut the inner
flue ensuring that the length between the inner and outer flue is
maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the
flue).
Once cut to the required length, ensure that the flue is free from
burrs and reassemble the flue. If fitting the flue from inside of the
building attach the outer wall seal to the flue terminal and push
the flue through the hole, once the wall seal has passed through
the hole, pull the flue back until the seal is flush with the wall.
Alternatively, the flue can be installed from outside of the building,
the outer seal being fitted last.
Should the flue require extending, the flue connections are push fit,
however, one flue bracket should be used to secure each metre of
flue.
Note: See table for maximum and minimum flue runs.
Level
* Min slope: 1˚
1˚= 17.5mm per metre
INSTALLATION
150 mm
Level
Fig. 3
/
17

Advertisement

Table of Contents
loading

Table of Contents