Fitting the Coaxial Flue
(Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall, fi t the rubber fl ue
seal into the internal fl ue turret (see diagram opposite),
insert the elbow into the socket and rotate to the required position.
Note: It is possible to rotate the elbow 360° on its vertical axis.
Using the fl ue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal fl ue kit (3318073) supplied is suitable for an
exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face
of the fl ue elbow (X - Fig 2), this fi gure must now be subtracted from
753mm, you now have the total amount to be cut from the plain end
of the fl ue.
Draw a circle around the outer fl ue and cut the fl ue to the required
length taking care not to cut the inner fl ue, next cut the inner
fl ue ensuring that the length between the inner and outer fl ue is
maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the fl ue).
Once cut to the required length, ensure that the fl ue is free from burrs
and reassemble the fl ue. If fi tting the fl ue from inside of the building
attach the grey outer wall seal to the fl ue terminal and push the fl ue
through the hole, once the wall seal has passed through the hole, pull
the fl ue back until the seal is fl ush with the wall. Alternatively, the
fl ue can be installed from outside of the building, the grey outer seal
being fi tted last.
Should the fl ue require extending, the fl ue connections are push fi t,
however, one fl ue bracket should be used to secure each metre of fl ue.
Note: See table for maximum and minimum fl ue runs.
In the event that extension pieces need to be shortened, they must
only be cut at the male end and it must be ensured that the inner and
outer fl ue remain fl ush.
Fig. 3
Installation without extension
Installation with extension
slope
* pente
Slope min 1° per metre
Clamp
Screws
Seal
installation
Level
Level
* pente 5 mm par mètre
max 3° per metre (1° = 17mm)
150 mm
Fig. 4
19