ABB ACSM1 Firmware Manual page 59

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

2.12
FBA MAIN CW (continued from previous page)
Bit
Name
10
JOGGING 2
11
REMOTE
CMD
12
RAMP OUT
0
13
RAMP HOLD 1
14
RAMP IN 0
15
EXT1/EXT2
16
REQ
STARTINH
17
LOCAL CTL
18
FBLOCAL
REF
19...27 Not in use
28
CW B28
29
CW B29
30
CW B30
31
CW B31
Val.
1
Activate jogging function 2. See section
page 43.
0
Jogging function 2 disabled
1
Fieldbus control enabled
0
Fieldbus control disabled
1
Force Ramp Function Generator output to zero.
Drive ramps to a stop (current and DC voltage lim-
its in force).
0
No operation
Halt ramping (Ramp Function Generator output
held).
0
No operation
1
Force Ramp Function Generator input to zero.
0
No operation
1
Switch to external control location EXT2.
0
Switch to external control location EXT1.
1
Activate start inhibit.
0
No start inhibit
1
Request local control for Control Word. Used when
the drive is controlled via PC tool or panel or
through local fieldbus.
- Local fieldbus: Transfer to fieldbus local control
(control via fieldbus control word or reference).
Fieldbus steals the control.
- Panel or PC tool: Transfer to local control.
0
Request external control.
1
Request fieldbus local control.
0
No fieldbus local control
Freely programmable control bits.
Information
Jogging
Parameters and firmware blocks
59
Log.
Par.
on
OR
10.14
-
-
-
-
-
-
-
-
OR
34.01
-
-
-
-
-
-
-
-

Hide quick links: