ABB ACSM1 Firmware Manual page 214

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

214
Code
Fault
(fieldbus code)
0040
ENCODER2
(0x7381)
0045
FIELDBUS COMM
(0x7510)
Programmable fault:
COMM LOSS FUNC
0046
FB MAPPING FILE
(0x6306)
0047
MOTOR OVERTEMP
(0x4310)
Programmable fault:
MOT TEMP PROT
0049
AI SUPERVISION
(0x8110)
Programmable fault:
AI SUPERVISION
Fault tracing
Cause
Encoder 2 feedback fault
EnDat or SSI encoder is used in
continuous mode as encoder 2.
[I.e.
90.02 ENCODER 2 SEL
(3) FEN-11 ABS
and
91.02 ABS ENC INTERF
ENDAT
or
(4) SSI
and
91.30 ENDAT MODE
CONTINUOUS
MODE
=
(1)
CONTINUOUS).]
Cyclical communication
between drive and fieldbus
adapter module or between
50.02
PLC and fieldbus adapter
module is lost.
Drive internal fault
Estimated motor temperature
(based on motor thermal model)
has exceeded fault limit defined
45.01
by parameter
45.04 MOT TEMP
FLT
LIM.
Measured motor temperature
has exceeded fault limit defined
by parameter
45.04 MOT TEMP
FLT
LIM.
Analogue input AI1 or AI2 signal
has reached limit defined by
parameter
13.13 AI SUPERVIS
13.12
ACT.
What to do
See fault ENCODER1.
If possible, use single position transfer
instead of continuous position transfer (i.e. if
encoder has incremental sin/cos signals):
=
- Change parameter
ENDAT MODE
=
(2)
Otherwise use Endat/SSI encoder as
encoder 1:
- Change parameter
=
(1)
to value
(or
91.25 SSI
90.02 ENCODER 2 SEL
Note: The new setting will only take effect
after parameter
used or after the JCU control unit is powered
up the next time.
Check status of fieldbus communication. See
appropriate User's Manual of fieldbus adapter
module.
Check fieldbus parameter settings. See
parameter group
Check cable connections.
Check if communication master can
communicate.
Contact your local ABB representative.
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
Check motor thermal model settings,
parameters
THERM
Check that actual number of sensors
corresponds to value set by parameter
MOT TEMP
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
Check analogue input AI1/2 source and
connections.
Check analogue input AI1/2 minimum and
maximum limit settings, parameters
and
13.03
91.25 SSI MODE
to value
(0) INITIAL
90.01 ENCODER 1 SEL
(3) FEN-11 ABS
and parameter
to value
90.10 ENC PAR REFRESH
50 FIELDBUS
on page 149.
45.06...45.08
and
45.10 MOT
TIME.
SOURCE.
/
13.07
and 13.08.
/
91.30
POS..
(0)
NONE.
is
45.02
13.02