4. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
Table 9-2: Input Parameters
Parameter
Voltage U
Current I
Power P
i
Capacitance C
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation
test required by EN60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in a Zone 0 environment.
N1 ATEX Type n
Certificate:
Standards:
Markings:
Special Condition for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation
test required by EN60079-15. This must be taken into account when
installing the apparatus.
ND ATEX Dust
Certificate:
Standards:
Markings:
26
BAS00ATEX1166X
EN60079-0:2012 + A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (–55 °C ≤ T
i
i
i
BAS00ATEX3167X
EN60079-0:2012 + A11:2013, EN60079-15:2010
II 3 G Ex nA IIC T5 Gc (–55 °C ≤ T
BAS01ATEX1427X
EN60079-0:2012 + A11:2013, EN60079-31:2009
II 1 D Ex t IIIC T50 °C T50060 °C Da
≤ +70 °C)
a
®
HART
30 V
200 mA
0.9 W
0.012 μF
≤ +70 °C)
a
Emerson.com/Rosemount