Setting And Verifying The Combustion Setting - Westinghouse WGRGH20**75F Series Installation, Start-Up, Maintenance, Parts, Warranty

Residential gas hybrid water heaters
Table of Contents

Advertisement

40
Do not fire (operate) the water heater until all connections have
been completed and the heat exchanger is filled with water. Doing
so will damage the water heater and void the warranty.
F. Setting and Verifying the Combustion Setting
1. After the water heater has fired, flip DIP switch three (3) in Group 1 to
the ON position (low fire). Proceed to check heater combustion values.
NOTE: Use a calibrated combustion analyzer to ensure CO and CO2
values are within the range shown in Table 24.
It is required to use a calibrated combustion analyzer to verify final
adjustment according to the combustion chart (Table 24). Failure to
do so could result in serious personal injury or death.
If the readings obtained are lower or higher than the combustion
readings in Table 24, use a T40 Torx screwdriver to adjust the offset
screw in a clockwise (positive) or counterclockwise (negative) direction
(approximately 1/4 turn). See Figure 41. Check your combustion values.
Repeat this procedure until the values obtained on the calibrated
combustion analyzer agree with those stated in Table 24.
NOTE: If the heater makes a whistling sound (harmonics) at low fire,
adjust the offset screw in a clockwise (positive) direction (approximately
1/8 turn). Check your combustion values and ensure they agree with
those stated in Table 24 before proceeding.
It is very important that the combustion system be set within the
recommended CO measurements listed in Table 24. Visually looking
at the burner does not determine combustion quality. Failure to
measure combustion with a calibrated combustion analyzer and set
the throttle within the recommended CO measurements could result
in property damage, severe personal injury, or death.
Natural Gas
Fan Speed
Low
CO PPM
<30
CO
(%)
8 - 9 1/2
2
Table 24 - Combustion Settings
2. When low fire settings have been obtained, flip DIP switch three (3)
in Group 1 to its original (OFF) position. This will return the heater to
normal operation.
3. Open a hot water faucet or faucets and run hot water at more than
2 gpm to put the water heater into high fire. Again check combustion
readings with a calibrated combustion analyzer.
NOTE: DO NOT adjust the gas valve offset screw at high fire. The offset
screw is only used to adjust combustion values at low fire.
4. When complete, turn off the hot water faucet(s). Allow water heater
to operate normall. Ensure it is operating properly.
5. Use a Phillips Head screwdriver to reinstall the heater top cover.
whl-605 Rev. 002 Rel. 000 Date 1.23.19
LP Gas
High
Low
<50
<50
8 1/2 - 10
9 - 10 1/2
9 1/2 - 11
High
<100
Figure 41 - Gas Valve Detail