Power Venting, Indoor Combustion Air In Confined Or Unconfined Space - Westinghouse WGRGH20**75F Series Installation, Start-Up, Maintenance, Parts, Warranty

Residential gas hybrid water heaters
Table of Contents

Advertisement

3. Power Venting, Indoor Combustion Air in Confined or Unconfined Space

This heater requires fresh, uncontaminated air for safe operation
and must be installed in a mechanical room where there is adequate
combustion and ventilating air. NOTE: To prevent combustion air
contamination, see Table 6.
Combustion air from the indoor space can be used if the space has
adequate area or when air is provided through a duct or louver to
supply sufficient combustion air based on the water heater input.
Never obstruct the supply of combustion air to the water heater. If
the water heater is installed in areas where indoor air is contaminated
(see Figure 23) it is imperative that the water heater be installed as
direct vent so that all combustion air is taken directly from the outdoors
into the water heater intake connection.
Unconfined space is space with volume greater than 50 cubic feet per
1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected
directly to this space, through openings not furnished with doors, are
considered part of the space.
Confined space is space with volume less than 50 cubic feet per
1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected
Model
Water Heater Capacity
75F / 76F
Max. 75,000 Btu/Hr.
100F
Max. 100,000 Btu/Hr.
Table 14 - Minimum Air Supply to Water Heater
DO NOT PLACE
DRYER NEAR
WATER HEATER
OR BOILER
Figure 23 - Do Not Place Appliance Near Dryer
directly to this space, through openings not furnished with doors,
are considered part of the space.
When drawing combustion air from inside a conventionally
constructed building to a confined space, such space should be
provided with two permanent openings: one located 6" (15 cm)
below the space ceiling, the other 6" (15cm) above the space floor.
Each opening should have a free area of one square inch per 1,000
Btu/hr (22cm 2 /kW) of the total input of all appliances in the space,
but not less than 100 square inches (645cm 2 ).
If the confined space is within a building of tight construction, air for
combustion must be obtained from the outdoors as outlined in the
Venting section of this manual. See Figures 24 and 25.
Insufficient air supply used with a Power Vented appliance may
cause the building to experience negative pressure inside.
Negative pressure is not allowable by most building codes and
can cause back drafting of cold air from outside through the unit,
potentially freezing the heat exchanger / tank.
Outside Air Area
Inside Air Area
20 sq. in.
25 sq. in.
LP-325-X
Minimum Required Air Volume
75 sq. in.
100 sq. in.
whl-605 Rev. 002 Rel. 000 Date 1.23.19
31
3,750 cu. ft.
5,000 cu. ft.