Wiring Example - Omron K8AK-AW Series Manual

Single-phase overcurrent/undercurrent relay
Hide thumbs Also See for K8AK-AW Series:
Table of Contents

Advertisement

Connections
Terminal Diagram
K8AK-AW1 100-240VAC
A
B
Relay Output
Control Output
Common
Relay output
250 VAC, 5 A (resistive load)
21
30 VDC, 5 A (resistive load)
B Power Supply Voltage
100 to 240 VAC
24 VAC/DC
A1
A2
(No polarity)
Note: 1. Do not connect anything to terminals that are shaded in gray.
2. There is no polarity for the DC power supply input.
3. For the current input, you can input only from the C terminal and one other terminal.
4. Refer to Setting Ranges and Wiring Connections on the I1, I2, and I3 current input terminals.
5. Use the recommended ferrules if you use twisted wires.
6. The K8AK-AW3 is designed to be used in combination with the OMRON K8AC-CT200L Current Transformer (CT).

Wiring Example

Directly Inputting a Current
Single-phase
power supply
21
24
C
I2
Power
A2
supply voltage
A1
A1
A2
11
12
21
24
24
22
C
I2
A1
A2
A2
A1
11
12
Load
22
I3
I1
14
A Current Input
22
AW1
I3
C
I2
I3
100 mA max.
500 mA max.
20m A max.
I1
I1
Relay Output
14
Common
11
12
14
Using a CT
Single-phase
power supply
Power
supply
AC/DC
Power
A2
supply voltage
A1
K8AK-AW
AW2
AW3
C
I2
I3
C
I2
I3
CT
5 A max.
100 A max.
CT
200 A max.
1 A max.
I1
I1
CT
21
24
22
C
I2
I3
A1
A2
I1
11
12
14
Load
Power
supply
AC/DC
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

K8ak-aw1K8ak-aw2K8ak-aw3K8ak-aw1 24 vac/dcK8ak-aw1 100-240 vacK8ak-aw2 24 vac/dc ... Show all