Three-phase voltage, asymmetry, and phase-sequence phase-loss relay
Table of Contents

Advertisement

Connections

Terminal Diagram

K8DT-PZ1 C N
(1) (2)
(1) Input Voltages
PZ1
PZ2
Phase-to-phase voltage:
200 to 240 VAC
3-phase,
3-phase,
3 W
3 W
power
power
supply
supply
L1
L2
L3
Note: Do not connect anything to terminals that are shaded in gray.

Wiring Example

Relay Output
L1
3-phase
L2
voltage
L3
L1
L2
L3
DIP SW
12
14
11

Timing Charts

Overvoltage, Undervoltage, Phase Sequence, and Phase Loss Operation Diagram
Overvoltage set value
L1
Input
L2
L3
Undervoltage set value
Flashing
Alarm indicator
Delay time: 250 ms
(reference value)
Contacts 11-14 or
transistor output
t
t1: Power ON lock (1 s)
t1
Phase Loss Operation
L1
Input L2
L3
Lit
Lit
Lit
Alarm indicator
Contacts 11-14 or
transistor output
Note: 1. The K8DT-PZ@ output contacts are normally operative.
2. The power ON lock prevents unnecessary alarms from being generated
during the unstable period when the power is first turned ON. There is no
contact output during timer operation.
3. Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected
when any of the phase-to-phase voltages goes below 60% of the rated input.
4. L1 and L2 are also used for the power supply. If the voltage becomes very
low, the Relay will not operate.
5. Phase loss (on power supply side and load side) is not detected in the motor
load during operation.
L1
Phase-to-phase voltage:
380 to 480 VAC
L1
L2
DIP SW
L3
14
Motor
Power
supply
AC/DC
Hysteresis: Fixed at 2%
Hysteresis: Fixed at 2%
Flashing
Lit
Lit
t
t: Operating time (0.1 to 30 s)
Delay time: 250 ms
(reference value)
t: Operating time (0.1 to 30 s)
t: Operating time (0.1 to 30 s)
Phase sequence Operation
L2
L1
L3
L1
L1
L3
L2
L2
L3
L2
L1
L3
Flashing
Flashing
Flashing
L2
L3
(2) Output
C: Relay Output
T: Transistor Output
12
12
14
11
11
Inside
Transistor Output
L1
3-phase
L2
voltage
L3
Note: Use copper wires with a rating of 75°C or an equivalent rating.
Hysteresis: Fixed at 2%
Asymmetry set value
Flashing
Lit
Delay time: 250 ms
(reference value)
Operation Table
t
Item
Normal
Overvoltage
Undervoltage
Asymmetry
Phase loss
Phase
sequence
*1. L1 and L2 are also used for the power supply. If the
voltage becomes very low, the indicator will turn OFF.
*2. The indicator will flash once per second after an
incorrect phase is detected and once per 0.5 second
during the detection time.
K8DT-PZ
14
11
Inside
L1
L2
L3
DIP SW
14
11
PLC
Indicators
OUT_LED
ALM_LED
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON *1
OFF
Flashing *2
Moter
Power
supply
AC/DC
Output
operation
ON
OFF
OFF
OFF
OFF
OFF