Omron K8AK-AS Manual

Omron K8AK-AS Manual

Single-phase current relay
Hide thumbs Also See for K8AK-AS:

Advertisement

Quick Links

Single-phase Current Relay
K8AK-AS
Ideal for Current Monitoring for
Industrial Facilities and Equipment.
• Monitor for overcurrents or undercurrents.
• Use commercially available CTs (CT current on secondary
side: 0 to 1 A or 0 to 5 A).
• Manual resetting and automatically resetting supported by one
Relay.
• Startup lock and operating time can be set separately.
• One SPDT output relay, 5 A at 250 VAC (resistive load).
• Output relay can be switched between normally open and
normally closed.
• Output status can be monitored using LED indicator.
• Inputs are isolated from the power supply.
Refer to Safety Precautions on page 9.
Refer to page 8 for commonly asked questions.
Ordering Information
List of Models
Setting range
Power supply voltage
2 to 20 mA AC/DC,
24 VAC/DC
10 to 100 mA AC/DC,
100 to 240 VAC
50 to 500 mA AC/DC
0.1 to 1 A AC/DC,
24 VAC/DC
0.5 to 5 A AC/DC,
100 to 240 VAC
0.8 to 8 A AC/DC
24 VAC/DC
10 to 100 A AC*,
20 to 200 A AC*
100 to 240 VAC
*1 The K8AK-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.)
Accessory (Order Separately)
●OMRON CT
Appearance
Input range
10 to 100 A AC,
20 to 200 A AC
Model
K8AK-AS1 24 VAC/DC
K8AK-AS1 100-240 VAC
K8AK-AS2 24 VAC/DC
K8AK-AS2 100-240 VAC
K8AK-AS3 24 VAC/DC
K8AK-AS3 100-240 VAC
Applicable
Model
Relay
K8AK-AS3
K8AC-CT200L
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
●Commercially Available CTs*
CT current on secondary
Appearance
side
0 to 1 A AC,
0 to 5 A AC
* If you use a commercially available CT, do not exceed the overload
capacity of the K8AK-AS2.
Applicable Relay
K8AK-AS2
1

Advertisement

Table of Contents
loading

Summary of Contents for Omron K8AK-AS

  • Page 1 20 to 200 A AC* 100 to 240 VAC K8AK-AS3 100-240 VAC *1 The K8AK-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) Accessory (Order Separately) ●OMRON CT ●Commercially Available CTs*...
  • Page 2 1 s at 600% * CT capacity on primary side. *1 The range is selected using connected terminals. *2 The K8AK-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not possible.) Ratings 24 VAC/DC...
  • Page 3: Specifications

    Overload capacity K8AK-AS3: Continuous input at 120%, 30 s at 200%, and 1 s at 600% with an OMRON CT (K8AC-CT200L) Note: Overload capacity of primary side of CT. ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, DC or 50/60 Hz sine wave input)
  • Page 4: Wiring Example

    4. Refer to Setting Ranges and Wiring Connections on the I1, I2, and I3 current input terminals. 5. Use the recommended ferrules if you use twisted wires. 6. The K8AK-AS3 is designed to be used in combination with the OMRON K8AC-CT200L Current Transformer (CT). Wiring Example...
  • Page 5 K8AK-AS Nomenclature ●Indicators Front Item Meaning Terminal block Power indicator (See notes 1 and 2.) Lit when power is being supplied. (PWR: Green) Relay status indicator Lit when relay is operating. (RY: Yellow) Lit when there is an overcurrent or un- dercurrent.
  • Page 6: Dip Switch Settings

    Malfunctions may occur if the input is connected to unused terminals and the Unit will not operate correctly. K8AK-AS3 Terminal I1 is not used by the K8AK-AS3. If using the OMRON K8AC-CT200L CT, connect to terminals k and l on the K8AC-CT200L. Power supply (Terminals kt and lt are not used.) voltage ●Power Supply...
  • Page 7 81.5 33.5 30 dia. 14.5 14.5 Note: The OMRON Current Transformer (CT) is designed to be used with the K8AK-AS3. Use terminals k and l for connections. (Terminals kt and lt are not used.) Optional Parts for DIN Track Mounting ●DIN Tracks...
  • Page 8: Questions And Answers

    30 s, and it is possible to perform overload load current. The K8AK-AS@ has a built-in filter as a detection. countermeasure against high frequencies and cannot be...
  • Page 9: Safety Precautions

    K8AK-AS Safety Precautions Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/. Warning Indications CAUTION Indicates a potentially hazardous situation CAUTION which, if not avoided, may result in minor or Electrical shock may cause minor injury.
  • Page 10: Precautions For Safe Use

    K8AK-AS Precautions for Safe Use Precautions for Correct Use 1. Do not use or store the product in the following locations. Observe the following operating • Locations subject to water or oil methods to prevent failure and • Outdoor locations or under direct sunlight malfunction.
  • Page 11: Terms And Conditions Agreement

    Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements.
  • Page 12 The Netherlands IL 60173-5302 U.S.A. Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 © OMRON Corporation 2014-2021 All Rights Reserved. OMRON (CHINA) CO., LTD. OMRON ASIA PACIFIC PTE. LTD. In the interest of product improvement, Room 2211, Bank of China Tower, No.

Table of Contents