Current Limit Setpoint And Source; Outdoor Temperature (Standard Report); Ice Termination Setpoint/Ice Termination Setpoint Source - Trane RTHC Installation Operation & Maintenance

175-450 ton units (60 hz); 125-450 ton units (50 hz)
Table of Contents

Advertisement

Chilled Water Setpoint and Source/Evap Leaving
Water Temp (Standard Report)
Chilled Water Setpoint [source]:
Evap Leaving Water Temp:
This is the actual setpoint currently in use by the
chiller. The "source," from where it is derived, can be
either External, Tracer or Reset (meaning reset is
enabled); otherwise the source is not displayed and
Front Panel setoint source is implied.
If the chiller is in the ice making or ice making
complete state, the following display is substituted for
the above display:
Ice Termination Setpt [source]:
Evap Entering Water Temp:
where source, if displayed is Tracer; otherwise it's
the Front Panel.
NOTE: The setpoint source may change
automatically from the implied "Front Panel "(no
source displayed) to "Tracer" if Tracer is
communicating a chilled water setpoint to the chiller.
The only way to override Tracer-communicated
setpoints is through the operator setting menu
(global setpoint override).
Reset Chilled Water Setpoint and Type/Starting
Chilled Water Setpoint and Source (Standard
Report)
The following will only be displayed if chilled water
reset is enabled:
[reset type] CWS:
[source] CWS:
with [reset type] being outdoor air reset, return reset,
or constant return reset and [source] being Front
Panel, External, or Tracer.
The first line displays the actual setpoint to which the
chiller is controlling, as reset upward depending on
the reset type, reset ratio, and maximum reset
parameters set elsewhere on the operator settings
menu.
Installation, Operation and Maintenance
xxx.x F
xxx.x F
or
xxx.x F
xxx.x F
xxx.x f/c
xxx.x f/c
The second line displays the fundamental
temperature (and its source) upon which the reset is
based. This represents the lowest setpoint possible
when no reset is applied.
Ice Termination Setpoint/Ice Termination
Setpoint Source (Standard Report)
If the ice building option is installed and the chiller is
not in the ice making or ice making completion mode,
the following is displayed:
Ice Termination Setpt [source]:
Press (Next) (Previous) To Continue
where the "source" is Tracer or the Front Panel (no
source field display).
Evaporator Entering and Leaving Water
Temperatures (Standard Report)
Evap Entering Water Temp:
Evap Leaving Water Temp:
Condenser Entering and Leaving Water
Temperatures (Standard Report)
Dashes "-------" will be displayed for the condenser
entering or leaving water temperature if the
corresponding input is open or shorted
Cond Entering Water Temp:
Cond Leaving Water Temp:
Current Limit Setpoint and Source (Standard
Report)
Current Limit Setpoint [source]:
Press (Next) (Previous) To Continue
If the source is displayed, it is Tracer, External, or ice
building.

Outdoor Temperature (Standard Report)

If the outdoor air temperature input is open or
shorted, and neither outdoor air reset nor low
ambient lockout is enabled, "-------" (dashes) is
xxx.x F
xxx.x F
xxx.x F
xxx.x F
xxx.x F
xxx%
5 - 9