Mechanical and Electrical Installation
4.4.1
Setting the Station Number of Analog Modules by Means of
DIL Switch Block S1
Basic Requirement
DIL switch block S1 is in the default position (as delivered). In the default
position the single DIL switch is set to E (for Electronic parameterization via
the bus) and the seven DIL switches in the array for setting the station num-
ber are set to 1 (see Figure 4-28).
Figure 4-28
If you leave the switches in their default positions, all you have to do is set
the station number when parameterizing via the bus (see Chapter 5).
If you set the single DIL switch to M (for Manual setting by DIL switches)
you must use the seven DIL switches in the array to set the station number
(see Figure 4-29).
4-44
1
0
1
DIL Switch Block S1 in Default
Position (As Delivered)
DIL Switch Block in Default Position (As Delivered)
E
Electronic Param-
eterization via
S1
Bus
2
4
8
16
32
64
M
Manual Setting
by Means of DIL
Switches
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b