6. Insert ventilator into the unit to the far left side,
making sure to clear the right filter bracket. Once
the ventilator is fully inserted, slide the ventilator
to the right until it is tight against the back of the
control panel (see Figure 3).
IMPORTANT NOTE: Position front lip of ventilator
over front grille and on top of condenser partition
(see Figure 3 inset). This is important to ensure
proper drainage of any water entering damper
assembly.
CAUTION: HOLE IN ERV-F MUST
CAUTION: HOLE IN ERV-F MUST
BE USED TO ENSURE CLEARANCE
BE USED TO INSURE CLEARANCE
FROM CONDENSER COIL TUBING
FROM CONDENSER COIL TUBING
SERVICE DOOR
FIGURE 3 (INSET)
LIP OF ERV IS TO BE
BETWEEN THE CONDENSER
GRILL AND SERVICE DOOR
FRONT GRILLE
Manual 2100-701
Page
8 of 16
7. Remove outer and inner control panel covers.
8. Remove female plug of high voltage wiring harness
(3-pin plug) from the heat recovery assembly
and snap into unit control panel (from inside
control panel) in the hole provided. Wire to top of
compressor contactor per wiring diagram (on ERV).
Connect high voltage plugs back together (see
Figure 3).
FIGURE 3

Install Ventilator

WHEN INSTALLING ERV-F POSITION
SO THAT HOLE IN FROM LIP IS
CENTERED OVER HOLE IN CONDENSER
GRILLE TO INSERT A SELF DRILLING
SCREW
SIDE SECTION VIEW
HIGH & LOW VOLTAGE
TO PLUG IN SIDE OF
CONTROL PANEL
HEAT RECOVERY
VENTILATOR
CONDENSER
PARTITION
MIS-4004