Error Messages In Position Decoding And Counting Mode - Siemens Simatic S5 IP 240 Manual

Counter/positioning/position decoder module
Hide thumbs Also See for Simatic S5 IP 240:
Table of Contents

Advertisement

Error Messages
14.2

Error Messages in Position Decoding and Counting Mode

14.2.1 Parameter and Data Errors
In position decoding and counting mode, the FB parameter and the DB data are checked by the
standard function blocks. If an error is detected, the error code is entered in DW 13 of the speci-
fied data block.
Table 14-3. Parameter and Data Errors in Position Decoding and Counting Mode
Error code
(DW 13)
0001
0002
0003
0004
0101
0102
0103
0104
0105
0106
0107
0108
0111
0112
0113
0114
0115
0116
0117
0118
0120
0121
0122
0201
0202
0203
0204
0205
0206
0207
0208
0210
0211
0212
0213
14-2
Description
Illegal module address
Illegal channel number
Error in configuring parameter
FB incompatible with IP firmware
Invalid initial value for track 1
Invalid initial value for track 2
Invalid initial value for track 3
Invalid initial value for track 4
Invalid initial value for track 5
Invalid initial value for track 6
Invalid initial value for track 7
Invalid initial value for track 8
Invalid final value for track 1
Invalid final value for track 2
Invalid final value for track 3
Invalid final value for track 4
Invalid final value for track 5
Invalid final value for track 6
Invalid final value for track 7
Invalid final value for track 8
Invalid zero offset
Invalid hysteresis
Invalid initial count
Limit values for track 1 cannot be transferred *
Limit values for track 2 cannot be transferred *
Limit values for track 3 cannot be transferred *
Limit values for track 4 cannot be transferred *
Limit values for track 5 cannot be transferred *
Limit values for track 6 cannot be transferred *
Limit values for track 7 cannot be transferred *
Limit values for track 8 cannot be transferred *
* Limit values cannot be transferred because track not configured
Channel not configured
Control FB illegal for configured mode or data block
Illegal function number (FKT)
Illegal control bit combination
IP 240
EWA 4NEB 811 6120-02a

Advertisement

Table of Contents
loading

Table of Contents