● Two screws with a maximum thread diameter of 4.8 mm
● Two plastic securing brackets
Please refer to the accessories list for the relevant order numer in section System
components (Page 23)
Procedure for mounting on a level surface
Step
5.2.3

Installing the diagnostics module in a control cabinet door/switchboard

Requirements
● A mounting cut-out measuring H x W 55 x 92 mm must be available.
● The control cabinet door/control panel must be no more than 16 mm thick.
NOTICE
Overall depth
Please observe the installation depth of 41 mm for the device.
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
Operating instruction
1
Insert the securing brackets into the openings
provided on the device until they engage.
2
Hold the device up to the surface prepared for
screw fastening.
3
Insert the screws through the oblong holes in the
securing brackets.
4
Screw the device onto the level surface so that it
is secure.
Description of the hardware
5.2 Mounting/installing/attaching
Figure
65