Diagnostics / service

8.1

Error management

Display concept
In error management, the following display concept applies:
● Errors that relate to the device are indicated by a
● Errors that relate to the sensors are indicated by a
● If more than one error is present at the same time,
Error management
A number of methods are available for diagnosing errors.
● Diagnostics with diagnostics module (Page 243)
● Diagnostics via LEDs (Page 238)
● Diagnostics with MSS ES (Page 256)
● Diagnostics with data sets (Page 270)
● Diagnostics with DP interface (Page 226)
Error management makes a distinction between four different error categories:
● Device error
● System error
● Sensor or wiring fault
● Parameterization or configuration error
Device error
A device error causes the system to stop. Communication between the modules is not
possible. These errors are caused by internal system errors.
This error category can occur in any operating mode.
Display on the central unit
LED
Display
DEVICE
RED
SF
RED
Modular Safety System 3RK3
System Manual, 10/2008, 926 2530-02 DS 02
Remedy
The central unit can only exit the system stop by means of a restart after switching
the power supply off and on. If the error is still present after the system has been
rebooted, you must replace the central unit.
Exception:
In the event of overvoltage/undervoltage, the device LED does not light up:
red
SF LED.
flashing red
SF LED.
red
red flashing
has priority over