Mitsubishi Electric MXZ-8B48NA Technical & Service Manual page 75

Hfc utilized r410a, split-type, heat pump air conditioners, outdoor unit, branch box
Hide thumbs Also See for MXZ-8B48NA:
Table of Contents

Advertisement

SW2 setting
Outdoor heatsink temperature (TH8)
– 40~200 (°C)
ON
– 40~327 (°F)w
1
2 3 4 5 6
LEV-6 opening pulse
ON
0~500
1
2 3 4 5 6
LEV-7 opening pulse
ON
0~500
1
2 3 4 5 6
LEV-8 opening pulse
ON
0~500
1
2 3 4 5 6
High pressure (63HS)
ON
0~500 (0.1 kgf/cm²)
0~711 (PSIG)w
1
2 3 4 5 6
Input current
0~50
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
TH5 Indoor-A
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
TH5 Indoor-B
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
TH5 Indoor-C
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
TH5 Indoor-D
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
ON
TH5 Indoor-E
1
2 3 4 5 6
w SW1-8 : OFF (Unit: °C, 0.1 kgf/cm²), SW1-8 : ON (Unit: °F, PSIG)
Display detail
75
Explanation for display
– 40~200 (°C), – 40~327 (°F)
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
(When the thermistor detects 100: or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0~500
0~500
0~500
0~500 (0.1 kgf/cm²), 0~711 (PSIG)
(When it is 100 or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~50
– 39~88 (°C)
– 38~190 (°F)w
– 39~88 (°C)
– 38~190 (°F)w
– 39~88 (°C)
– 38~190 (°F)w
– 39~88 (°C)
– 38~190 (°F)w
– 39~88 (°C)
– 38~190 (°F)w
Unit
°C
°F
Pulse
Pulse
Pulse
0.1 kgf/cm²
PSIG(w)
A
°C
°F(w)
°C
°F(w)
°C
°F(w)
°C
°F(w)
°C
°F(w)