SW2 setting
Thermo ON time until error stops
0~999
ON
1
2 3 4 5 6
Target rotation of outdoor fan motor
ON
1
2 3 4 5 6
Sub-cool (Heating mode)
ON
1
2 3 4 5 6
Code of the difference between room
temperature and set temperature
(" Tj": 0 - 99 °C)
Tens digit of code: current Tj
Units digit of code: Tj a minute ago
ON
1
2 3 4 5 6
U9 Error status during the Error
postponement period
ON
1
2 3 4 5 6
Display detail
SW1
4
5
6
Indoor unit 1
0
0
0
Indoor unit 2
1
0
0
Indoor unit 3
0
1
0
Indoor unit 4
1
1
0
Indoor unit 5
0
0
1
Indoor unit 6
1
0
1
Indoor unit 7
0
1
1
Indoor unit 8
1
1
1
71
Explanation for display
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs.
0~999
0~130
Code of the difference between room temperature and
set temperature (" Tj")
Cooling
Tj
Tj
= room temp. Set temp.
0
Tj
0.5
1
1.0 < Tj
0.5
2
0.5 < Tj
0.5
3
0.0 < Tj
0.0
4
0.5 < Tj
0.5
5
1.0 < Tj
1.0
6
1.5 < Tj
0.5
7
2.0 < Tj
2.0
8
2.5 < Tj
2.5
9
3.0 < Tj
3.0
SW setting (1-4, 5, 6)
Target unit
000
Indoor unit 1
100
Indoor unit 2
010
Indoor unit 3
110
Indoor unit 4
001
Indoor unit 5
101
Indoor unit 6
011
Indoor unit 7
111
Indoor unit 8
Description
Normal
Power circuit board
Overvoltage error
Controller circuit board
Undervoltage error
Power circuit board
L1 or L2 phase interruption error
Power circuit board
Abnormal power synchronous signal
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
0.5secs.
2 secs.
4
15
Heating
Tj
= Set temp. room temp.
Tj
0.5
0.5 < Tj
0.0
0.0 < Tj
0.5
0.5 < Tj
1.0
1.0 < Tj
1.5
1.5 < Tj
2.0
2.0 < Tj
2.5
2.5 < Tj
3.0
3.0 < Tj
3.5
3.5 < Tj
Detection point
Display
00
—
01
02
04
08
Unit
Minute
rpm
:
Code
display
Code
display