8.2 Remote Panels (Optional)

Kohler Co. offers three remote panels for connection to
the generator set:
D
A panel with a start/stop switch
D
A panel with a start/stop switch and two gauges
(engine oil pressure and water temperature)
D
A panel with a start/stop switch and four gauges (DC
voltmeter, engine oil pressure, water temperature,
and hourmeter)
If difficulty with the remote operation occurs, test the
switch, gauges, and gauge senders using the following
procedures. See Section 10, Voltage Reconnection and
Wiring Diagrams.
Generally, if the sender changes its resistance values as
its respective pressure/temperature changes, it is
working correctly. An inoperative sender will either be
Component
Ohmmeter Connections
Remote switch: yellow/red wire
Remote
terminal and black wire terminal.
start/stop
switch
Remote switch: grey/black wire
terminal and black wire terminal.
Generator set
Connect the red test lead to P3-4
ON light,
and black test lead to P3-1.
gauge lights,
DC voltmeter,
and hourmeter
Water
Connect the red test lead to P3-4
temperature
(socket side) and black test lead
gauge
to P3-2 (socket side).
Oil pressure
Connect the red test lead to P3-4
gauge
(socket side) and black test lead
to P3-3 (socket side).
Note: Check continuity of gauge wiring and extension harness before replacing components.
Figure 8-5 Remote Start Panels Troubleshooting
TP-5936 7/04
open or shorted. Refer to Figure 8-3 and Figure 8-4 for
resistance
troubleshooting information on the remote start panels.
Temperature
60_C (140_F)
90_C (194_F)
100_C (212_F)
Figure 8-3 Water Temperature Sender Resistance
Pressure
0 kPa (0 psi)
345 kPa (50 psi)
690 kPa (100 psi)
Figure 8-4 Oil Pressure Sender Resistance
Procedure
Place the ohmmeter on the R x 1
scale. Press the rocker switch to the
START position.
Place the ohmmeter on the R x 1
scale. Press the rocker switch to the
STOP position.
Place the controller rocker switch to
the START position. Stop the
generator set when the test is
complete. Generator set does not
need to be running, just cranking for
this test. Note: If the hourmeter is
not illuminated, test it by connecting
it to a 12-volt battery. Note: The
hourmeter is polarity sensitive.
Start the generator set for the test.
Start the generator set for the test.
values.
Refer
to
2-Meter and 4-Meter Panels
Resistance
134 ± 10 ohms
51.5 ± 4 ohms
38 ± 3 ohms
2-Meter and 4-Meter Panels
Resistance
135 ohms
Results
Continuity, the switch is
functional. Open, replace switch.
Continuity, the switch is
functional.
If 12-volts DC is present and the
component does not function
after the J3 is connected to the
controller P3, replace the
component(s).
If 0.5--12-volts DC is present and
the gauge does not function after
the J3 is connected to controller,
replace the gauge.
If 0.5--12-volts DC is present and
the gauge does not function after
the J3 is connected to the
controller, replace the gauge.
Section 8 Component Troubleshooting
Figure 8-5
for
10 ohms
80 ohms