4.0

TECHNICAL DATA

Model Number
GENERAL DATA
Product I.D. Number
Classification
Input (gross) min-max
Input (net) min-max
Recovery Rate (44° ΔT)
Recovery Rate (50° ΔT)
Heat generator seasonal efficiency
Shipping Weight
NO
X
NO
Class
X
GAS DATA G20
Nominal gas inlet pressure
Maximum gas inlet pressure
Minimum gas inlet pressure
Gas flow rate – m
3
/hr
Flue gas mass rate (@ 9.0% CO
Gas inlet connection size
GAS DATA G31
Nominal gas inlet pressure
Maximum gas inlet pressure
Minimum gas inlet pressure
3
Gas flow rate – m
/hr
Flue gas mass rate (@ 9.0% CO
Gas inlet connection size
ELECTRICAL DATA
Power consumption
Power supply
Protection class
WATER DATA
Water content
Water connections (F & R)
Max. water pressure
Min. water pressure
Maximum water temperature
4.1.1
TECHNICAL DATA
)
2
)
2
TTW410
CE 0063BS3806
II
2H3B/P
kW
55.4 - 444
kW
50 - 400
l/hr
8168
l/hr
7188
%
95.4
kg
400
mg/kWh
44
6
mbar
20
mbar
25
mbar
17.5
m3/hr
5.3 - 42.3
g/sec
24.1 - 207.8
" BSP
2
mbar
37
mbar
45
mbar
27
m3/hr
16.8
g/sec
193
" BSP
2
W
752
Single phase 230v/50Hz
IPX0B
litres
30
" BSP
2 ½
bar
8
bar
1
°C
70
TTW580
75.5 - 611
68 - 550
11263
9912
95.9
450
41
7.2 - 58.2
2
23
265
2
829
43
8
1
70
10