Wiring
6.9 Wiring the MPI / PROFIBUS DP bus connectors
See also
Network components of MPI/DP and cable lengths (Page 4-35)
6.9.2

Setting the terminating resistor on the bus connector

Bus connector: Plugging it into module
1. Plug the wired bus connector into the module.
2. Screw-tighten the bus connector on the module.
3. If the bus connector is located at the beginning or end of a segment, you must enable the
Please make sure during startup and normal operation that power is always supplied to
nodes where the terminating resistor is active.
6-16
Note
Use a bus connector with 90° cable exit.
terminating resistor (switch setting "ON"; see the following figure).
Note
6ES7 972-0BA30-0XA0 bus connectors are not equipped with a terminating resistor. You
cannot insert this type of bus connector at the beginning or end of a segment.
S7-300, CPU 31xC and CPU 31x: Installation
Operating Instructions, Edition 08/2004, A5E00105492-05