1.2

Design

2
Siemens Building T
echnologies
Cerberus Division
The BeamRex DLO1191 comprises:
Base DLB1191A consisting of:
Terminal support with terminals
The base is required already at the time of installation. The base housing features six
PG16 tapped cable inlets.
Detector module DLA1191A consisting of:
Transmitter
Receiver
Lens
Electronics
The plug-in detector module is inserted just prior to commissioning.
The lens can be optimally aligned to the reflector by means of the adjustment set.
Reflectors
Different reflectors are available for different distances:
5 to 30m
30 to 50m
50 to 65m
20 to 100m
Short distance filter
For shorter distances between 5 and 10 m an additional short distance filter is required:
5 to 8m
7 to 10 m
Filter against external light influences DLF1191-AC
The detector is rarely influenced by external light. If, however, powerful external light
causes interference, the filter DLF1191-AC can be used to eliminate this.
Accessories:
Detector heater DLH1191 for DLO1191, against condensation of the lens
Auxiliary tools:
Detector adjustment set DZL1191 consisting of:
Adjustment device
Test filter
Aiming device
Reflector foil DLR1193 (10 x 10cm) 1 pc.
Reflector foil DLR1192 (20 x 20cm) 1 pc.
Reflector foil DLR1192 (20 x 20cm) 4 pcs.
Prism made of glass DLR1191 (cat's eye) 1 pc.
with built-in heating against condensation
DLF1191-AB
DLF1191-AA
e1276e