Monitoring Areas With Flat Ceilings; Monitoring Areas With Sloping Ceilings; Additional Dlo1191'S On The Slope Of The Ceiling - Siemens Cerberus DLO1191 Manual

Linear smoke detector
Hide thumbs Also See for Cerberus DLO1191:
Table of Contents

Advertisement

4.4

Monitoring areas with flat ceilings

Distance from ceiling min. 30cm,
max. 60cm for rooms <10m high
(section 4.10)
4.5

Monitoring areas with sloping ceilings

4.5.1

Additional DLO1191's on the slope of the ceiling

Siemens Building T
echnologies
Cerberus Division
Min. gap between two parallel
beams determined by distance
DLO11.. and reflector
(section 4.9)
Fig. 11 Detector layout in areas with flat ceilings
To be defined as «sloping», a ceiling must have an angle of inclination of at least 11°
which corresponds to 20cm/m. With gable roofs which have a slope of >0.5, always ar-
range a monitoring beam in the gable area.
Example:
Calculation of the slope n
The number of DLO1191's required results from the maximum permissible monitoring
width shown in section 4.11
1/4
1/4
Fig. 12 Arrangement with 3 monitoring beams on a sloping ceiling
min. 30cm
n
a
n + a
b
1/4
1/4
Distance between DLO11.. and
reflector 5 ... 100m
Max. width of monitored
area determined by height
of room (section 4.11)
4m
+ 0, 4
b
10m
19
e1276e
09.2000