6
Commissioning
6.1
Settings
32
Siemens Building T
echnologies
Cerberus Division
Remove the detector cover
Set the DIP switches
The DLO1191 can be operated either on an interactive DS11 line or a collective line. The
choice between collective and interactive line is made with DIP switch [S4].
The detector has 3 sensitivity settings («Reduced», «Standard», «Increased»). The re-
sponse threshold is set with DIP switch [S1], [S2].
The transmitter intensity (strong, weak) can be set with DIP switch [S3].
The DIP switch [S3] which governs the transmitter intensity is set to «strong» by default. If
the signal amplitude is too high (display on the adjustment unit: Range = 13, signal > 50),
the transmitter can be set to «weak». If the measurement section is ≤10m, a supplemen-
tary filter must be installed.
Function
Reduced sensitivity
Standard sensitivity
Increased sensitivity
Weak transmitter signal
Strong transmitter signal
Collective system
Interactive system
Reserve
«S6 ON»
Alarm at beam interruption
(< 60s)
«S6 OFF»
Fault at beam interruption
(< 30s)
* Operating conditions according to BS 5839: Part 5
Fig. 33 Settings
S1
S2
S3
# # # #
# # # #
ON
OFF
# #
# #
# #
# #
ON
ON
# # # #
# # # #
OFF
OFF
# #
# #
ON
OFF
# #
# #
# # #
ON
# # #
# # #
# # #
OFF
# # # #
# #
# # # #
S4
S5
S6
ON
OFF
# #
# #
*
# # # #
ON
# # # #
OFF
# #
e1276e
09.2000