Derating curves
NOTICE
Siemens AG
6SE7087-2NP85-0AA0
SIMOVERT MASTERDRIVES
Permissible rated input voltage in %
according to VDE 0110 / IEC 664-1
(not required by UL / CSA)
100
75
50
0
1000
Height above sea level in m
Permissible rated current in %
100
90
80
70
60
0
1000
Height above sea level in m
Permissible rated current in %
100
75
50
25
0
0
10
20
Coolant temperature in °C
Fig. 9-1
Derating curves
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 45 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
⇒ Total derating = 0.845 x 1.25 = 1.056 (= 1)
Operating Instructions
2000
3000
4000
2000
3000
4000
30
40
50
x Derating
altitude
ambient temperature
Technical Data
Height
Derating
[m]
factor K
1
1000
1.0
2000
0.9
3000
0.845
4000
0.8
Temp
Derating
[°C]
factor K
2
50
0.879
45
1.0
40
1.125
35
1.25 *
30
1.375 *
25
1.5 *
*See note
below
K
= 0.845
1
K
= 1.25
2