Connecting-up
5
1
6
9
X91 – "Fault" output
2
1
X92 - "Pulse
disable" output
2
1
7-10
Pin
Designation
1
n.c.
2
n.c.
3
RS485P (USS)
4
n.c.
5
Ground
6
P5V
7
n.c.
8
RS485N (USS)
9
n.c.
Table 7-9
RS485 interface
If a fault occurs in the rectifier unit the fault message is output via the
contacts of the signaling relay and the main contactor is de-energized.
At the same time the red LED lights up on the front panel.
In the event of a fault, the contact is open.
The possible causes for a fault are described under the "Displays,
messages" section.
Terminal
Designation
2
T. 13
1
T. 14
Connectable cross-section: 2.5 mm² (AWG 12)
Terminal 1 is at the front when installed.
Table 7-10
"Fault" output
As long as the pulse disable is set, either there is a fault or the unit is
still pre-charging.
The contact is therefore open.
Inverter pulse disable is canceled as soon as the unit switches to the
"RUN" state.
Terminal
Designation
2
T. 13
1
T. 14
Connectable cross-section: 2.5 mm² (AWG 12)
Terminal 1 is at the front when installed.
Table 7-11
"Pulse disable" output
Meaning
Do not connect!
Do not connect!
Data via RS485 interface
Do not connect!
Reference potential to P5V
5 V aux. voltage supply
Do not connect!
Data via RS485 interface
Do not connect!
Meaning
Fault
Fault
Meaning
Pulse disable
Pulse disable
6SE7087-2NP85-0AA0
Operating Instructions
05.2005
Range
RS485
0 V
+5 V, max. 200 mA
RS485
Range
I max = 1 A, 24 V
I max = 1 A, 24 V
Range
I max = 1 A, 24 V
I max = 1 A, 24 V
Siemens AG
SIMOVERT MASTERDRIVES