4.3
Configure GSV flow measurement
The gas standard volume (GSV) flow measurement parameters control how volume flow is
measured and reported in a gas application.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time.
Choose one or the other.
4.3.1
Configure Volume Flow Type for gas applications
ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Standard Gas
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement is
used.
Restriction
Gas standard volume measurement is incompatible with some applications. Set Volume Flow Type
to Liquid if you are using any of the following applications:
•
•
•
•
Procedure
Set Volume Flow Type to Gas Standard Volume.
4.3.2
Configure Standard Density of Gas
ProLink III
Field Communicator Configure > Manual Setup > Measurements > GSV > Gas Ref Density
Configuration and Use Manual
If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and
0 will be used in all internal processing.
Device Tools > Configuration > Process Measurement > Flow
Volume
Petroleum measurement
Concentration measurement
Fuel consumption
Production Volume Reconciliation (PVR)
Device Tools > Configuration > Process Measurement > Flow
Configure process measurement
27