Changing the function of the terminals
The function of the terminals marked in color in the two figures above, can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set using default settings ("p0015 Macro drive unit").
The factory settings of the terminals for USS/Modbus and PROFIBUS/PROFINET described
above correspond to the following default settings:
● p0015 = 12
– Setting using the commissioning tools STARTER, Startdrive and the IOP operator
– Setting using the BOP-2 operator panel: "Std ASP"
● p0015 = 7
– Setting using STARTER, Startdrive and the IOP operator panel: "Fieldbus with data
– Setting using BOP-2: "FB cdS"
Further default settings can be found in the Operating Instructions, see also: Manuals for
your inverter (Page 31).
CU240B-2 and CU240E-2 Control Units
Compact Operating Instructions, 04/2015, A5E35792002B AA
panel: "Standard I/O with analog setpoint"
set switchover"
3.4 Terminal strips on CU240E-2 Control Units
Installing
17