ASSEMBLY
The fryer must be restrained to prevent tipping and the splashing of hot liquid. The means
of restraint may be the manner of installation, such as connection to a battery of appliances,
installing the fryer in an alcove, or by separate means such as adequate ties.
Note: The gas supply pressure at gas inlet should be less than 3.5 kPa.
FLUE CONNECTION
Make the flue connection as follows:
Comply with Vapor Removal from Cooking Equipment, ANSI-NFPA
Standard #96 (latest edition), available from the National Fire Protection Association
Batterymarch Park, Quincy, MA 02269
Locate the fryer under a hood with adequate connection to an exhaust duct.
The hood must extend 6" (15 cm) beyond fryer on both sides.
Clearance above the fryer should be adequate for combustion byproducts
to be removed efficiently.
An 18" (46 cm) minimum clearance should be maintained between the flue vent
and the filters of the hood venting system.
Never make flue connections directly to the fryer.
Do not obstruct the flow of the gases from the appliance.
Proper air balance should be maintained in the room.
6