Maintenance Using Shc1 Handheld Interrogator; Introduction; Inspection - Honeywell Searchpoint Optima Plus Operating Instructions Manual

With optional hart output
Hide thumbs Also See for Searchpoint Optima Plus:
Table of Contents

Advertisement

MAN0905_Issue 7_07/17
SHC1 Handheld Interrogator
Read this chapter if the SHC1 Handheld Interrogator is being used to communicate
with Searchpoint Optima Plus.
Note: The instructions that follow assume that the SHC1 is switched on, in Optima+ mode, in the Main
Menu. See Chapter 8 "Use of the SHC1 Handheld Interrogator" for details.

10.1 Introduction

This chapter explains how to perform common maintenance operations. Please refer to IEC/EN 60079-29-
2 or other local or national regulations for guidance on establishing an appropriate maintenance routine.
The instructions assume that the SHC1 is switched on, in Optima+ mode, in the Main Menu. See Chapter 8
"Use of the SHC1 Handheld Interrogator" for details.

Inspection

Inspection of a unit fitted with a Flow Housing
Bump Test (Gas Challenge)
Bump Test (Gas Challenge) with RGC
Re-zero Searchpoint Optima Plus
Calibration
View and Clear Faults or Warnings
Caution: After changing any parameter, poll the Searchpoint Optima Plus and verify that the received
value is correct.
Note: When connecting or disconnecting a multimeter, power off the Searchpoint Optima Plus, otherwise
the unit will indicate a latched warning that the 4-20 mA loop was broken. If this occurs it can be cleared
using the SHC1 Handheld Interrogator. See Clear Faults or Warnings.
10.2 Inspection
Searchpoint Optima Plus should be inspected periodically and cleaned if necessary. The required frequency
of inspection will depend on local site conditions and will need to be established through experience.
Caution: Gas readings may be generated during this procedure.
1. Select Calibrate then Display to inhibit the 4-20 mA output signal.
2. Inspect the Searchpoint Optima Plus unit, its junction box and cabling for any signs of physical damage.
3. Using a ½ inch / 13 mm A/F open ended spanner, unscrew the two retaining nuts and remove the
Standard Weather Protection.
4. Inspect the Standard Weather Protection for damage or build up of debris / contaminants. If required,
clean or replace weather protection.
5. Inspect the Dust Barrier and clean or replace if required.
6. Remove the Dust Barrier and inspect the optics.
7. Clean any dust or contaminants from the optics using mild detergent and a soft cloth or cotton bud.
Do not use solvents or abrasive cleaners.
10. Maintenance using
How to check and clean the unit
How to check and clean a unit fitted with a flow housing
How to carry out a gas test using the Gassing Cover
How to carry out a gas test using the Remote Gassing Cell
How to re-zero if gas test results are unacceptable
How to calibrate the zero (and span if required)
How to view Faults and Warnings
Searchpoint Optima Plus with optional HART
42
output
®
Operating Instructions
2108M0550