Double Hole Lug - Alcatel-Lucent 9768 User Manual

Metro radio outdoor b4
Table of Contents

Advertisement

Installing an 9768 MRO B4
....................................................................................................................................................................................................................................
The following image shows a long barrel double hole crimp lug:
Figure 3-20 Double hole lug
...................................................................................................................................................................................................
3
Attach the ground cable to the 9768 MRO B4 chassis using the M6 hardware provided in
the ground kit (M6x16 screw, lock washer, plain washer).
Clean the contact surface area and use an antioxidant to avoid oxidation. Torque the M6
fasteners to 4.5 Nm (3.3 lb ft).
...................................................................................................................................................................................................
Route and attach the ground wire to the site ground system. An extra double hole crimp
4
lug, included in the ground kit, may be used if appropriate or the customer can provide
the necessary components to attach the ground wire to the site ground.
Clean the contact surface area and use an antioxidant to avoid oxidation.
E
N D
O F
...................................................................................................................................................................................................
Connecting the power connector
There is a danger of electric shock when the power cord is energized.
The connection/disconnection of the power cord to the 9768 MRO must be done only with
the power cord de-energized. De-energize the far end of the power cord from the power
source prior to disconnection at the 9768 MRO end.
....................................................................................................................................................................................................................................
Alcatel-Lucent 9768 MRO
3MN-MRO-AWS-IMOP
Issue 1 February 2014
Long barrel double hole crimp lug
(1/4" hole, ¾" spacing)
S T E P S
CAUTION
Electric-shock hazard
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
Procedure 3-1: Installing the 9768 MRO B4 onto a wall or
pole
3-15

Hide quick links: