EMC Directive. The finished plant does not More information on approvals and certificates, are require CE marking. However, the installation available at www.danfoss.com. Search for approval or must comply with the essential requirements of certificate. the directive. This is assumed by the use of appliances and systems that are CE-labeled under the EMC Directive.
Machinery Directive. Drives without a safety function do not fall under the Machinery Directive. If a drive is Drives with an integrated safety function must comply integrated into a machinery system, Danfoss can provide with the machinery directive. information on safety aspects relating to the drive.
Individual harmonic current I public low voltage distribution system having an input current of ≤16 A per phase. Four emission classes are 2.2–4 kW (3.0–5.0 defined: Class A through D. The Danfoss drives are in Class 35.29 35.29 7.11 5.14 hp), 380–480 V...
(656 ft) altitude. measurement in each of the 3 motor phases or in the DC • Above 2000 m (6561 ft) altitude, contact Danfoss link. A short circuit between 2 output phases causes an regarding PELV. overcurrent in the inverter. The inverter turns off when the...
IE1 = state of the art. • IE2 = above state of the art. Danfoss drives fulfill energy efficiency class IE2. The energy efficiency class is defined at the nominal point of the CDM. Power drive systems (PDS) Torque-producing current [%]...
4.2.4 Comparison of Energy Savings Volume % Illustration 4.6 Energy Savings at Reduced Fan Capacity The Danfoss drive solution offers major savings compared with traditional energy-saving solutions. This is because the drive is able to control fan speed according to thermal 4.2.3 Example of Energy Savings...
Discharge dampers reduce power consumption somewhat. 1650rpm Inlet guide vans offer a 40% reduction but are expensive to install. The Danfoss drive solution reduces energy consumption with more than 50% and is easy to install. 1350rpm 4.2.5 Example with Varying Flow over 1...
The Drive Configurator automatically generates an 8-digit sales number to be delivered to the local sales office. Furthermore, it can produce a project list with several products and send it to a Danfoss sales representative. To access the Drive Configurator, go to: www.danfoss.com, and search for drive configurator.
3) Applies to dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com and search for ecoSmart.
Page 54
3) Applies to dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com and search for ecoSmart.
Design fuses for protection in a circuit capable of supplying a maximum of 100000 A (symmetrical), 480 V maximum. See Table 6.7 and Table 6.8 for circuit breaker capacity for Danfoss CTI25M circuit breaker at 480 V maximum.
Page 66
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.