Typical Field Wiring Diagram; Electrical Data - York H5CE150A50 Installation Manual

Split-system condensing unit (air cooled) world 50 hz
Table of Contents

Advertisement

292424-XIM-A-0307
INDOOR
Sol
C
G
W1
W2
FIGURE 1 - TYPICAL FIELD WIRING DIAGRAM
TABLE 4: ELECTRICAL DATA
Unit Power
Model
Supply
H3CE150A50
380/415-3-50
H4CE180A50
380/415-3-50
H3CE240A50
380/415-3-50
1.
RLA and LRA values are for one (1) compressor.
2.
Dual element, time delay type fuses or HACR circuit breakers.
3.
HACR type per NEC.
Unitary Products Group
THERMOSTAT
R
C
W1
W2
Y1
SPLIT SYSTEM CONNECTION
DIAGRAM
Compressor
1
1
Qty.
RLA
LRA
2
13.9
94
2
19.2
110 / 118
2
18.3 /24.3
127 / 158
Y2
G
X
Condenser Fan Motor
Qty.
Hp/kW
FLA
2
1/.75
2.2/2.0
2
1/.75
4.0/3.6
2
1/.75
4.0/3.6
OUTDOOR
TB3
G1
Sol
POS1
LIMIT
SD
R
24/120 VAC
SD
OUTPUTS
SD
C1
Y1
C2
R
C
PO 1
G
PO 2
Y1-OUT
Y2
Y1-ECON
X
HPS2
C
LPS2
HPS1
LPS1
LOW AMB
FAN OVER
Unit
Min. Circuit
Max. Fuse
Ampacity
Breaker Size
(Amps)
(Amps)
35.7
45
51.2
70
55.0
80
2
/
3
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

H5ce240a50H5ce180a50H5ce150H5ce180H5ce240